所示图像仅为示意图。请从产品数据表中获得准确的规格。
| Type | Description |
|---|---|
| product certifications | ATEXBVCCCCEBECCSADNVEZUGLGOSTRINASETITSEULLROS |
| product weight | 0.26 kg |
| mounting position | HorizontalVertical |
| [Ith] conventional free air thermal current | 23 A conforming to IEC 60947-4-1 |
| height | 89 mm |
| breaking capacity | Icu = 50 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2Icu = 3 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2Icu = 15 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2Icu = 6 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2Icu = 4 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| suitability for isolation | Yes conforming to IEC 60947-1 |
| device short name | GV2ME |
| network type | AC |
| power dissipation per pole | 2.5 W |
| control type | Pushbutton |
| product or component type | Circuit breaker |
| operating rate | 25 cyc/h |
| motor power kW | 11 kW at 500 V AC 50/60 Hz9 kW at 400/415 V AC 50/60 Hz18.5 kW at 690 V AC 50/60 Hz |
| mechanical robustness | Vibrations 5 Gn, 5...150 Hz conforming to IEC 60068-2-6Shocks 30 Gn for 11 ms conforming to IEC 60068-2-27 |
| connections - terminals | Lugs-ring terminals - external diameter : 9.5 mmBars- 6 x 9.5 mm |
| poles description | 3P |
| mounting mode | By clipsBy screws |
| width | 45 mm |
| phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| mounting support | Rail |
| magnetic tripping current | 327 A |
| operating altitude | 2000 m |
| rated duty | Continuous conforming to IEC 60947-4-1 |
| ambient air temperature for operation | -20...60 °C |
| mechanical durability | 100000 cycles |
| utilisation category | AC-3 conforming to IEC 60947-4-1Category A conforming to IEC 60947-2 |
| network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| tightening torque | 1.7 N.m - on lugs-ring terminals - screw M41.7 N.m - on bars - screw M4 |
| fire resistance | 960 °C conforming to IEC 60695-2-1 |
| protective treatment | TH |
| circuit breaker application | Motor protection |
| connection pitch | 13.5 mm without spreader |
| IK degree of protection | IK04 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-240 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-250 % at 440 V AC 50/60 Hz conforming to IEC 60947-275 % at 500 V AC 50/60 Hz conforming to IEC 60947-275 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| standards | CSA C22-2EN 60204IEC 60947-1IEC 60947-2IEC 60947-4-1NF C 63-120NF C 63-650NF C 79-130UL 508VDE 0113VDE 0660 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| depth | 78.2 mm |
| ambient air temperature for storage | -40...80 °C |
| trip unit technology | Thermal-magnetic |
| range of product | TeSys GV2 |
| electrical durability | 100000 cycles for AC-3 at 440 V |
| thermal protection adjustment range | 17...23 A |